FR wires & cables are used in a wide range of electrical applications like emergency systems, stand-by power supplies and elevators in subway substations, airports, public locations, hotels and hospitals. All tests of FR wires and cables are carried out in accordance with IEC 60502-1, BS 7846, BS 7211 and BS 6387 CAT CWZ in its own laboratories accredited by A2LA ISO/IEC 17025:2005.
Specification:
- Designation Type H07Z-R and H07Z-K BS 7211. Flame Retardant to IEC 60332-1 Vertical Flame Propagation Test. Products tested at internationally reputable labs, LPCB, BASEC & bsi.
Conductor:
- Soft annealed copper according to BS EN 60228, Class 2 stranded and Class 5 flexible conductor wrapped with mica tapes.
Insulation:
- Halogen free, low smoke cross-linked material (LS0H-XL) of Type EI 5 to EN 50363-5 90 °C. Colors are available upon request.
LPCB & BASEC Approvals:
- BS 6387 (CWZ) test under flame temperature 950 °C for 3 hour
- IEC 60331-21
- BS EN 50200(PH-120)
Special Requirements (upon request):
- Different packing options are available
Fire Resistant Cable Types: Single & Multi core cable unarmored, Multi core cable armored, Single core cable armored, Multi core cable armored
Specification:
- Electrical low voltage cables complying with IEC 60502-1 BS 7846. Our products tested at internationally reputable labs,LPCB, BASEC & bsi. All cable are Flame Retardant to IEC 60332-3.24 Category C Flame Propagation Test, Oil esistance and Sunlight & UV Resistant. Fire resistant test as per BS 6387 (CWZ) 950 °C for 3 hour.
Conductor:
- High conductivity soft annealed copper according to BS EN 60228, Class 1, Class 2 stranded and Class 5 flexible conductor wrapped with mica tapes. Conductor can be offered with round, round compacted and sectored shape.
Insulation:
- Cross-linked polyethylene (XLPE) with Maximum service temperature 90ºC.
Armoring (upon request):
- Aluminum Wire Armored “AWA” for single core cable.
- Galvanized steel wire “SWA” for multi core cable.
Outer Sheathing:
- Low Smoke & Fume Zero Halogen (LS0H)
Special Requirements (upon request):
- High flame propagation tests: IEC 60332-3.23 Category B – IEC 60332-3.22 Category A
- Fire performance: F120 – F2 – IEC 60331 – BS 6387 (CWZ)
- Water resistance
- Anti-termite resistant
- Shield type
- Polyvinyl chloride (PVC ST2) outer sheath
- Special color for insulation and outer sheath
- Different packing options are available